Products
DAM-E3022N
DAM-E3022N is a module with 8-channel isolated digital input and 8-channel isolated digital output, and it supports Ethernet communication interface and standard Modbus TCP protocol. It is equipped with a good human-computer interface, and it is easy to use and rich in functions.
Category:
Products
Data acquisition module
Ethernet module
Product description
Digital Input |
|
Input Channel |
8-Channel single-ended digital inputs (dry contact or wet contact common cathode) |
Digital Input Voltage |
Dry contact: logic level 0: open circuit Logic Level 1: Ground Wet Contact: Logic level 0: 0~+3V (max) Logic level 1: +10V~+30V Default factory: dry contact mode jumper |
Operating Mode |
DI input, low-to-high latch, high-to-low latch, counter, frequency measurement |
Maximum Filter Frequency |
5KHz |
Support counter function |
32 bit |
Counter/Frequency Input Range |
0.2~3KHz |
Others |
Support DI reverse function |
Digital Output |
|
Output Channel |
8-Channel open-drain output (source) |
Output Voltage |
10-30VDC |
Output Current |
1A max per channel |
Output Frequency |
0~5KHz |
Operating Mode |
DO output, low to high delay output, high to low delay output, frequency output |
Others |
|
Isolation Voltage |
2000V |
Communication Interface |
10/100Mbps Ethernet |
Watchdog |
Dual watchdog |
Supply Voltage |
+10V~30VDC |
Power Protection |
Power reverse protection |
Power Consumption |
2W@24VDC |
Operating Temperature |
-10℃~+70℃ |
Storage Temperature |
-20℃~+80℃ |
Previous
Next
Previous
Next