Products

Product Related Downloads Related Products
+
  • DAM-3505H(R)-01.jpg
  • DAM-3505H(R)-02.jpg
  • DAM-3505H(R)-04.jpg
  • DAM-3505H(R)-03.jpg

DAM-3505H(R)

DAM-3505H(R) is a high-speed acquisition three-phase full-parameter AC power acquisition module, and it supports RS485 communication interface and standard ModbusRTU protocol. It is equipped with a good human-computer interface, so it is easy to use and its performance is stable.

Category:

Products

Data acquisition module

RS485 acquisition module


Close
  • Comparison

Product description

Analog Input

Input Channel

3 current channels, 3 voltage channels

Input Type

voltage input, current input

Voltage Range (RMS)

Default 400V (can be customized, maximum 450V)

Current Range (RMS)

Default 100A (customizable 1A, 5A, 10A, 20A, 30A, 50A, 60A, 80A,

100A, 120A, 150A, 200A, 250A, 400A, 500A)

Temperature and

Humidity Measurement

External temperature and humidity sensor (only supported by R module)

Output Parameters

Phase voltage, phase current, line voltage, active power, reactive power,

apparent power, power factor, total energy, forward active energy,

forward reactive energy, input frequency, three-phase total active power,

three-phase total reactive power, three-phase total apparent power,

three-phase total power factor, three-phase total positive-phase

active energy,three-phase total positive-phase reactive energy,

three-phase total power factor,humidity (only supported by the R module ), temperature(only supported by R module)

Note: The module with R suffix has the function of measuring ambient

temperature and ambient humidity, see 1.5 Comparison of different suffixes

Acquired Signal

The collected signal is the grid standard AC signal, and the frequency

does not exceed 65Hz

The Sampling Period

40ms~1000ms can be set, that is, 25Hz to 1Hz can be configured

Resolution

16 bit

Acquisition Accuracy

2‰

Current Transformer

External current transformer, see 1.6 External transformer description

Energy

with energy storage

Secondary Mutual

Inductance

with secondary mutual inductance function

Isolation Voltage

3000V

Others

Communication Interface

RS485

Baud Rate

1200~115200bps

Data Transfer Rate

Configurable passive upload or active upload

Active upload: the same sampling frequency, upload once for

every acquisition, up to 25Hz

Passive upload: According to 485 communication rate.

Watchdog

Built-in watchdog

Supply Voltage

+10V30VDC

Power Protection

Power reverse protection

Power Consumption

Rated 0.75W @ 24VDC

Operating Temperature

-10℃~+70℃

Storage Temperature

-20℃~+85℃