DAM-3018AA is an 8-channel signal relay output module, including 4-channel C-type relays and 4-channel A-type relays, each channel has LED indicator light indication, RS485 communication interface, and standard ModbusRTU protocol. It is equipped with a good human-computer interface, so it is easy to use and its performance is stable.

Category:

Products

Data acquisition module

RS485 acquisition module


Close
  • Comparison

Product description

Digital Output

Output Channel

There are 8 channels of signal relays, of which 4 channels

are C-type relays and 4 channels are A-type relays.

Contact Material

Ag+Au clad (silver+gold cladding)

Rated Control Capacity

 (Resistive Load) Note 1

2A, 30V DC

Contact Maximum Allowable Current (Resistive Load)

2A

Contact Maximum Switching Voltage (Resistive Load) Note 2

220V DC or 220V AC

Minimum Applicable Load (Resistive Load)

10µA 10mV DC

Relay Off Time

4ms (max)

Relay 0n Time

4ms (max)

Mechanical Life

More than 100 million times (on-off frequency 180 times/min)

Electrical Life

More than 100,000 times (under 2A 30V DC resistive load),

more than 500,000 times (under 1A 30V DC resistive load)

 (on-off frequency 20 times/min)

Operating Mode

DO output, low to high delay output, high to low delay output,

pulse output

Others

Communication Interface

RS485

RS485 Communication Rate Note 3

Maximum 180 times/second (total channel of single module,

under 115200bps)

Maximum 24 times/second (total channel of single module,

under 9600bps)

Maximum 3 times/second (total channel of single module,

under 1200bps)

Baud Rate

1200~115200bps

Watchdog

software watchdog

Supply Voltage

+10~30VDC

Power Protection

Power reverse protection

Power Consumption

Rated 0.5W @ 24VDC

Operating Temperature

-10℃~+70℃

Storage Temperature

-40℃~+80℃

 

Note

1. Resistive Load: The maximum value of all parameters of the relay is realized when the load is resistive load. Resistive load means the load that iodine tungsten lamp, incandescent lamp, resistance furnace, oven, electric water heater, etc. will not cause voltage and current phase changes.

2. Contact Maximum Switching Voltage: this value is the maximum value when the load is a resistive load, and supports DC and AC voltage. If the load is a capacitive load or an inductive load, this indicator may be reduced.

3. RS485 Communication Rate: This parameter refers to the communication speed between the MCU controller and the host computer, which belongs to the theoretical maximum value. The communication rate will also be affected by the length of the field wiring, the number of loaded modules, the programming architecture of the host computer, and the hardware capabilities of the CPU.